Delta Electronics — 7.4.1 Error Codes and LED Indicators for CPU Modules

AS Series Programming Manual _7 7-20 ERROR LED indicator status Error CPU Description code status Blinking Blinking Blinking ON OFF fast normally slowly 0302 The MCR instruction exceeds the range. Stop V 0D03 The operands used in DHSCS are not used properly. Stop V 0E05 The operands HCXXX used in DCNT are not used properly. Stop V 1300 - 130F Errors occurred in the remote modules Continue V 1402 The arrangement of the I/O modules is not consistent with the settings. Stop V 140B Number of communication modules exceeds the limit of four. Stop V 140D Number of extension modules exceeds the limit of 32.

Stop V 140E Number of remote modules exceeds the limit of eight on the right side of the CPU module. Stop V 1500 Connection lost in the remote modules Continue V 1502 - 150F Errors occurred in the remote modules Continue V 1600 The ID of the extension module exceeds the range. Stop V 1601 The ID of the extension module cannot be set. Stop V 1602 The ID of the extension module is duplicated. Stop V 1603 The extension module cannot be operated. Stop V 1604 Extension module communication timeout Stop V 1605 Hardware failure Stop V 1606 Errors on the communication module function card Stop V 1607 The external voltage is abnormal.

Stop V 1608 The Internal factory calibration or the CJC is abnormal. Stop V 1609 - 160F Reserved (Error codes for the extension modules) Stop V 1800 - 180F Errors occurred in the extension modules Continue V 1900 - 191C Heartbeat errors occurred in the slave of the CANopen communication module. Continue V 1950 The initialization of CANopen communication module has not yet been completed, the CANopen instructions cannot be executed. Continue V