Delta Electronics — 6.15.2 Explanation of Module Instructions

Chapter 6 Applied Instructions 12. See the sequence diagram in a calibration example. 6_ Explanation of the timing points in the above sequence diagram:   The LCCAL instruction is enabled and the CPoint value and the flags Trigger , Done , ADone and Error are all cleared automatically.   Trigger the calibration flag.   The instruction finds a module number error and displays the error code of LC module number error   Disable the LCCAL instruction.   After a trigger, the LC module completes the single-point calibration and the CPoint value is added by 1 and the Done flag changes to ON.   Clear the trigger signal flag Trigger.

  Subsequently, the Done flag is cleared by the instruction.   After a trigger, the LC module completes the entire calibration and the CPoint value is added by 1 and both of the flags Done and ADone change to ON. 6-437 Error code Description 16#1410 Error in the LC group number or module number 16#1411 The LC module has no such channel number 16#1412 LC module calibration timeout (set time:500ms) 16#1413 The LC module has completed the calibration. Disable the instruction and retrigger it.