Delta Electronics — 6.15.2 Explanation of Module Instructions

AS Series Programming Manual Explanation 1. This instruction is available for AS04RTD-A, AS06RTD-A, AS04TC-A and AS08TC-A with FW V1.06.00 or later and can only support the right-side modules. For PLC with FW V1.08.00 or later, it can support remote right-side modules as well. 2. The parameter settings are listed in the following table. _6 6-444 Operand Data type Function Setting range Description GROUP DWORD/DINT Group number The RTD/TC module group number that is connected to the right side of PLC directly or connected to the remote module that acts as PLC, e.g. the first connected module group is group number 1, the second connected module group is group number 2.

Up to 15 module group can be connected and counted. MODULE DWORD/DINT Module number The module number that is connected to the right side of PLC directly or connected to the remote module that acts as PLC, e.g. the first connected module is module number 1, the second connected module is module number 2. Up to 32 modules can be connected and counted and each type of modules should be included in the count. CH DWORD/DINT Channel number Channel number for PID algorithm, e.g. channel 1 is number 1 for PID algorithm and channel 2 is number 2 for PID algorithm and so forth. UPDATE BOOL Update the PID-related parameters True:Update PID related parameters in the module, such as PID RUN~CYCLE.

_ False: After updating is complete, it refreshes to False.