Chapter 6 Applied Instructions 6_ 6-445 Operand Data type Function Setting range Description PID RUN _ BOOL Enabling the PID algorithm True: use the PID algorithm. False: reset the output value (MV) to 0, and stop using the PID algorithm. SV DWORD/DINT Target value -32768~32767 Target value PID MODE _ DWORD/DINT PID control mode 0: Automatic control When PID MAN switches from _ True to False, invoke the output value (MV) in the automatic algorithm. 1: Auto tuning the parameters for the temperature control. After tuning is done, the system is in auto control mode (PID MODE is set _ to 0) and fill in the appropriate parameters (Kc Kp, Ti Ki, _ _ Td Kd, Tf, APPHA and BETA) _ Note:
when the mode is set to 1, auto tuning the parameter, you cannot set up the value. PID MAN _ BOOL PID A/M mode True: Manual Output the MV according to MOUT. This setting has no effect when PID MODE is set _ to 1. False: Automatic Output the MV according to the PID algorithm. MOUT AUTO _ BOOL MOUT automatic change mode True: Automatic MOUT value varies with the MV. False: Normal MOUT value does not vary with the MV.