Delta Electronics — 6.15.2 Explanation of Module Instructions

AS Series Programming Manual _6 6-448 Operand Data type Function Setting range Description whether the present error is less than the absolute value of ERR DBW, and _ checks whether the present error meets the cross status condition. If the present error is less than the absolute value of ERR DBW, _ and meets the cross status condition, the present error is counted as 0, and the PLC applies the PID algorithm ; otherwise the present error is brought into the PID algorithm. ALPHA DWORD/DINT Integral gain of the initialization value (heating up) 0~100 Unit:

1% Initial value compensation of integral calculus (for heating up) BETA DWORD/DINT Integral gain of the initialization value (cooling down) 0~100 Unit: 1% Initial value compensation of integral calculus (for cooling down) MOUT REAL MV 0~1000 (unit: 0.1%) When set to PID Manual