Chapter 6 Applied Instructions 6_ 6-449 Operand Data type Function Setting range Description (PID MAN=True), _ the MV value is outputted as the value set manually for MOUNT. BIAS REAL Feed forward output value -32768~32767 Feed forward output value, used for the PID feed forward. CYCLE DWORD/DINT Sampling time (TS) 1~1000 (unit: 100 ms) When the instruction is scanned, use the PID algorithm according to the sampling time, and refresh MV. MV REAL MV output value 0.0~100.0 (unit: 1%) MV output value PV DWORD/DINT/ REAL Present value Format is defined in HWCONFIG. I MV _ REAL Accumulated integral value Accumulated integral value is for reference.
When the MV is out of the range of 0-100%, the accumulated integral value in I MV stops _ changing. ERROR DWORD/DINT Error codes 16#0000:instruction is being executed and is working normally 16#1400:the module you are using does not support this instruction. 16#1401:group number or module number setting error 16#1402:the module you are using does not respond and communication time out