Delta Electronics — 6.15.2 Explanation of Module Instructions

AS Series Programming Manual Note: 1. If the PID parameter exceeds the upper limit, only the maximum value can be written in the module, if the PID parameter is below the lower limit, only the minimum value can be written in the module. 2. When PID_RUN switches from True to False, it clears the MV output value to 0. If you need to keep the last MV output value, you can switch the operand EN to False to close this instruction and the MV output value can be kept. Example 1. You need to set up the parameters before executing DMPID. Switch the operand EN from False to True to execute this instruction.

If you need to change parameters during execution, you can use the UPDATE flag to update the parameters (including PID_RUN ~ CYCLE) . After the parameters are updated, the system clears the flag UPDATE. 2. When M0 is ON, the instruction is executed. When M2 is ON, the DMPID starts to process. When M2 is OFF, MV value is 0. And the value in MV is stored in D16. When M0 is OFF, the instruction is not executed. And the values in the instruction is not changed. 3. When the mode is set to 1, the system starts to auto tuning the parameters for the temperature control.

After tuning is done, the system switches to auto control mode (PID_MODE is set to 0) and fill in the appropriate parameters (Kc_Kp, _6 Ti_Ki, Td_Kd, Tf, ALPHA and BETA) to data devices. You can also use retentive devices to retain PID parameters. 6-450 Operand Data type Function Setting range Description 16#1403:channel setting error