AS Series Programming Manual Dependent Formula & Derivative of PV ( PID_EQ=True & PID_DE=True ) BIAS dt dE T dt E T E K MV d − + = ∫ * 1 i c + t ( E = SV – PV ) 0 Or BIAS dt dE T dt E T E K MV d + + = ∫ * 1 t ( E = PV – SV ) i c + 0 2. When you set the PID_MODE to 1, auto tuning mode is enabled. When auto tuning is complete, the value becomes 0 and switches off the auto tuning mode automatically. PID Control Block Diagram:
PID Block Diagram (Independent) 1 PID_DIR E SV PV + - + REVERSE 0 X(-1) ERR_DBW >0 Kc_Kp BIAS PID_MAN 0 + + + 0 Kc_Kp 1 MV _6 PID-I >0 Ti_Ki 0 + + + MV_MAX, MV_MIN Ti_Ki Td_Kd + MOUT_AUTO MOUT 0 >0 MOUT 1 PID_MAN 0 0 1 MOUT Td_Kd, Tf 6-452 DEAD BAND PID-P MV LIMIT _ PID-D