Chapter 6 Applied Instructions PID Block Diagram (Dependent) + - + 1 E PID_DIR SV PV REVERSE 0 X(-1) Kc_Kp >0 ERR_DBW Kc_Kp 0 BIAS PID_MAN + + + 0 1 >0 Ti_Ki MV 0 MV_MAX, MV_MIN Ti_Ki MOUT_AUTO MOUT Td_Kd MOUT PID_MAN 0 >0 1 0 ERR_DBW Td_Kd, Tf 0 1 MOUT When the PV (present value) is in the range of ERR_DBW , at the beginning, the present error is brought into the PID algorithm according to the normal processing, and then the CPU module checks whether the present error meets the cross status condition: PV (present value) goes beyond the SV (target value). Once the condition is met, the present error is counted as 0 when applying the PID algorithm.
After the PV (present value) is out of the ERR_DBW range, 6_ the present error is brought into the PID algorithm again. If PID_DE is true, that means it uses the variations in the PV to calculate the control value of the derivative, and after the cross status condition is met, the PLC treats Δ PV as 0 to apply the PID algorithm. (Δ PV = current PV – previous PV ). In the following example, the present error is brought into the PID algorithm according to the normal processing in section A ,and the present error or Δ PV is counted as 0 to apply the PID algorithm in the section B. 6-453 DEAD BAND PID-P MV LIMIT _ PID-I PID-D