Wiring ASDA-B3 AL500: see the following diagram. When the motor runs normally, but both STO_A and STO_B signals are low for 10 ms at the same time, the firmware disables the drive (Servo Off) and 3 triggers AL500. STO_A STO_B Firmware detection of the STO function FDBK SRDY Alarm AL501 / AL502: see the following diagram. When the motor runs normally, but one of the safety signal source is low for 1 s, the firmware disables the drive (Servo Off) and triggers AL501 or AL502. The following diagram illustrates AL501. STO_A STO_B L Firmware detection of the STO function FDBK SRDY Alarm Note: 1. When the STO_A signal is low, AL501 occurs; when the STO_B signal is low, AL502 occurs. 2.
Contact the distributor if AL503 occurs. 3. Refer to Section 3.9.4 for the FDBK signal. 3-72 H L L H STO not active 10 ms STO active Max. 20 ms Close OFF AL500 Open OFF ON No alarm AL500 H L H STO not active 1 s STO active Max. 20 ms STO active Max. 20 ms Open Open OFF ON No alarm AL501