ASDA-B3 Test Operation and Panel Display 4.4.2 Force DO on You can switch to the Diagnosis mode by the following steps. Set P2.008 to 406 and enable the function to force DO on. Then, set the DO by binary method with P4.006. When the parameter 4 value is 2, it forces DO2 on. When the value is 5, it forces DO1 and DO3 on. No data is retained in this mode. The mode returns to the normal DO mode after cycling the power. You can also set P2.008 to 400 to switch to the normal DO mode. SET SET Force to enable DO mode SET Force DO1 on Force DO2 on Force DO3 on Force DO4 on Force DO5 on Force DO1 and DO3 on Force DO1, DO2, and DO3 on Note: P4.006 is displayed in hexadecimal format.
Therefore, it does not show the fifth 0. 4-11