Test Operation and Panel Display ASDA-B3 4.5.4 Trial run without load (Speed mode) Before starting the trial run without load, firmly secure the motor base to avoid any danger 4 caused by force generated by the motor during speed changes. Step 1: set the control mode of the servo drive to Speed mode. Set P1.001 to 2 for Speed mode. Then cycle the power to the servo drive. Step 2: in Speed mode, the following table lists the digital input settings for the trial run. This table shows the settings that disable the negative limit (DI6), positive limit (DI7), and emergency stop (DI8) functions. Thus, parameters P2.015 - P2.017 and P2.036 - P2.040 are set to 0 (disabled).
You can program the digital inputs of Delta’s servo drive. When programming the digital inputs for the servo drive, refer to Table 8.1 Digital input (DI) descriptions in Chapter 8. The default setting includes the negative limit, positive limit, and emergency stop functions. Therefore, if any alarm occurs after you complete the settings, cycle the power to the servo drive or set DI5 to On to clear the error. Refer to Section 4.5.2. 4-20 Digital input Parameter setting value Symbol Function description CN1 Pin No.
DI1 P2.010 = 101 SON Servo activated DI1- = 9 DI2 P2.011 = 109 TRQLM Torque limit DI2- = 10 DI3 P2.012 = 114 SPD0 Speed selection DI3- = 34 DI4 P2.013 = 115 SPD1 Speed selection DI4- = 8 DI5 P2.014 = 102 ARST Alarm reset DI5- = 33 DI6 P2.015 = 0 - DI disabled - DI7 P2.016 = 0 - DI disabled - DI8 P2.017 = 0 - DI disabled - DI9 P2.036 = 0 - DI disabled - DI10 P2.037 = 0 - DI disabled - DI11 P2.038 = 0 - DI disabled - DI12 P2.039 = 0 - DI disabled - DI13 P2.040 = 0 - DI disabled -