ASDA-B3 Test Operation and Panel Display The Speed command selection is determined by SPD0 and SPD1. See the following table. 4 0: the switch is open (off). 1: the switch is closed (on). The parameter setting range of the internal register is from -60000 to +60000. Speed setting = setting value x 0.1 rpm. For example, P1.009 = +30000, speed setting = +30000 x 0.1 rpm = +3000 rpm. Command setting for the speed register: Set P1.009 to +30000. Set P1.010 to +1000. Set P1.011 to -30000. Motor’s running direction: Step 3: 1. Switch on DI1 and the drive is in the Servo On state. 2. When both Speed commands of DI3 (SPD0) and DI4 (SPD1) are off, that means it executes the S1 command.
The motor rotates according to the analog voltage command. 3. When DI3 (SPD0) is on, that means it executes the S2 command. The rotation speed is 3000 rpm. 4. When DI4 (SPD1) is on, that means it executes the S3 command. The rotation speed is 100 rpm. 5. When both DI3 (SPD0) and DI4 (SPD1) are on, that means it executes the S4 command. The rotation speed is -3000 rpm. 6. You can repeat steps 3 - 5. 7. If you want to stop the motor, switch off DI1 (Servo Off).
4-21 CN1 DI signal Speed command Command source Content Range number SPD1 SPD0 S1 0 0 Mode S External analog signal Voltage difference between V-REF and GND -10V to +10V Sz N/A Speed command is 0 0 S2 0 1 Internal register parameter P1.009 -60000 to +60000 S3 1 0 P1.010 -60000 to +60000 S4 1 1 P1.011 -60000 to +60000 Input command Rotation direction + CCW (positive direction) - CW (negative direction)