Operation Mode ASDA-B3 6.4.3 Smooth Torque command Refer to Chapter 8 for detailed descriptions of the relevant parameter. 6 Target torque t P1.007 6.4.4 Scaling of the analog command The Torque command is controlled by the analog voltage difference between T_REF and GND. Adjust the torque slope and its range with P1.041. For example: 1. If you set P1.041 to 100 and the external input voltage is 10V, the Torque command is 100% of the rated torque. 2. If you set P1.041 to 300 and the external input voltage is 10V, the Torque command is 300% of the rated torque. Torque command The slope is set by P1.041.
input (V) Analog voltage Refer to Chapter 8 for detailed descriptions of the relevant parameter. 6-28 Parameter Function P1.007 Torque command smoothing constant (low-pass filter) 300% 100% 0 -5 5 1 -100% -300% Parameter Function P1.041 Maximum output for analog Torque command