Motion Control ASDA-B3 The following tables list the parameters for the torque limit (P1.087) and the torque limit time (P1.088). 7 Settings: This setting is only for the torque homing mode. As shown in the following figure, after homing is triggered, the motor runs in one direction and reaches the protector. The servo drive then outputs a larger motor current in order to counter the external force. The servo drive uses P1.087 and P1.088 as the conditions for homing. Since the hard stops are not always the same, it is recommended to return to find the Z pulse as the origin.
Torque level detection P1.087 Torque curve when the servo searches Torque curve the servo searches for for the hard stop Start point Z pulse Z pulse Note: the actual maximum torque output of the motor is 10% greater than the detected torque level (P1.087). For example: set P1.087 to 50%, then the maximum torque output of the motor is 60%. Settings: The setting of the level reached timer for the torque homing mode. Refer to P1.087 for the timing diagram of torque homing mode. 7-20 Address: 01AEH P1.087 Torque homing - torque level detection 01AFH Default: 1 Control mode: PR Unit: % Setting range: 1 - 300 Format: DEC Data size:
16-bit Protector Level reached timer P1.088 Maximum torque output 10% en es Protector Level reached timer P1.088 Maximum torque output en es Address: 01B0H P1.088 Torque homing - level reached timer 01B1H Default: 2000 Control mode: PR Unit: ms Setting range: 2 - 2000 Format: DEC Data size: 16-bit