Delta Electronics — 7.1.6 PR procedure execution flow

ASDA-B3 Motion Control (1 ms command cycle) (1 ms command cycle) PR executor 7 Motion command generator Time (a) Overlap command - Acceleration and deceleration time are different (1 ms command cycle) (1 ms command cycle) PR executor Motion command generator Time acceleration time of the 2 nd command (b) Overlap command - Acceleration and deceleration time are identical Figure 7.1.6.11 Overlap command Interpret PR path flow The PR paths mentioned above include commands such as Sequence, Interrupt, and Overlap. The replacement, integration, and overlapping for commands lead to different behavior depending on the settings. The suggested steps to interpret the PR path is as follows. 1.

Check the command sequence. Check whether there are delay time (DLY) and interrupt (INS) commands because these two types change the command execution sequence. 2. Find the lead PR and identify each PR group of 1 ms. 3. In each PR group of 1 ms, only the last motion command is executed. The Jump and Write commands are immediately executed in the PR executor. 4. Position commands are combined based on the principle described in Section 7.1.3.3.

7-57 PR#1 (O) PR#2 Position Position DLY=[0] 0 ms DLY=[0] 0 ms 5000 PUU 10000 PUU ABS ABS 200 rpm 500 rpm Acc=[0] 6.67 ms Acc=[0] 16.65 ms Dec=[0] 6.67 ms Acc=[0] 16.65 ms eed Deceleration time of the 1st command is different from acceleration time of the 2nd command PR#1 (O) PR#2 Position Position DLY=[0] 0 ms DLY=[0] 0 ms 5000 PUU 10000 PUU ABS ABS 200 rpm 500 rpm Acc=[0] 6.67 ms Acc=[2] 6.67 ms Dec=[0] 6.67 ms Dec=[2] 6.67 ms eed Deceleration time of the 1st command is identical to