Delta Electronics — P1.xxx Basic parameters

ASDA-B3 Parameters If the requirement is for the motor to run at 1,000 rpm, which corresponds to 8V, and its maximum Example 1: speed is 5,000 rpm, then the setting is: P1.004 = Maximum speed Ч 100% = Required speed 1000 rpm 5000 rpm Ч 100% = 20% 8 Refer to the following examples for the motor's current speed and corresponding voltage output: Settings: Refer to P0.003 for the analog output setting. Settings: 0: disable this function. Settings: 0: disable this function. Settings: 0: disable this function. 8-35 Motor speed MON1 analog monitor output 300 rpm MON1 = 8V × Current speed ×100% = 8V × 300 rpm ×100% = 2.4V Maximum speed ×P1 1.

00 004 5000 rpm× 12 00 0 900 rpm MON1 = 8V × Current speed ×100% = 8V × 900 rpm ×100% = 7.2V Maximum speed×P1 1. 00 004 5000 rpm× 12 00 0 Address: 010AH P1.005 MON2 analog monitor output proportion 010BH Default: 100 Control mode: All Unit: % (full scale) Setting range: 0 - 100 Format: DEC Data size: 16-bit Address: 010CH P1.006 Speed command smoothing constant (low-pass filter) 010DH Default: 0 Control mode: S / Sz Unit: ms Setting range: 0 - 1000 Format: DEC Data size: 16-bit Address: 010EH P1.007 Torque command smoothing constant (low-pass filter) 010FH Default: 0 Control mode: T / Tz Unit: ms Setting range: 0 - 1000 Format: DEC Data size: 16-bit Address: