Delta Electronics — 9.3 MODBUS communication protocol

MODBUS Communication ASDA-B3 Example 1: function code 03H, read multiple words When the master issues a read command to the first slave: 9 The slave reads two continuous words starting from the start data address 0200H. In the response message from the slave, the content of the start data address 0200H is 00B1H and the content of the second data address 0201H is 1F40H. The maximum allowable number of data in one single access is 10. ASCII mode: Command Message (Master): Response Message (Slave): RTU mode: Command Message (Master): Response Message (Slave): Note: a silent interval of 10 ms is required before and after each transmission in RTU mode.

9-6 Start ‘:’ ‘0’ Slave Address ‘1’ ‘0’ Function ‘3’ ‘0’ ‘2’ Start Data Address ‘0’ ‘0’ ‘0’ ‘0’ Data Number (in words) ‘0’ ‘2’ ‘F’ LRC ‘8’ End 1 (0DH) (CR) End 0 (0AH) (LF) Start ‘:’ ‘0’ Slave Address ‘1’ ‘0’ Function ‘3’ ‘0’ Data Number (in bytes) ‘4' ‘0’ ‘0’ Content of Start Data Address 0200H ‘B’ ‘1’ ‘1’ ‘F’ Content of the 2nd Data Address 0201H ‘4’ ‘0’ ‘E’ LRC ‘8’ End 1 (0DH) (CR) End 0 (0AH) (LF) 01H Slave Address 03H Function 02H (High) Start Data Address 00H (Low) 00H Data Number (in words) 02H C5H (Low) CRC (Check Low) B3H (High) CRC (Check High) 01H Slave Address 03H Function 04H Data Number (in bytes) 00H (High) Content of Start Data Address 0200H B1H (Low) 1FH (High) Content of the 2nd Data Address 0201H 40H (Low) A3H (Low) CRC (Check Low) D4H (High) CRC (Check High)