ASDA-B3 MODBUS Communication Communication data structure Definitions for the data frames in the two modes are as follows: ASCII mode: 9 Start Start character ‘:’ (3AH) Slave Address Communication address: 1 byte consists of 2 ASCII codes Function Function code: 1 byte consists of 2 ASCII codes Data (n-1) Data (0) Data content: n word = 2n-byte consists of 4n ASCII codes, n ≤ 10 ……. LRC Error check: 1 byte consists of 2 ASCII codes End 1 End code 1: (0DH) (CR) End 0 End code 0: (0AH) (LF) RTU mode: 9-5 Start A silent interval of more than 10 ms Slave Address Communication address: 1 byte Function Function code: 1 byte Data (n-1) Data content: n-word = 2n-byte, n ≤ 10 …….
Data (0) CRC Error check: 1 byte End 1 A silent interval of more than 10 ms