Delta Electronics — 10.3.4.1 Establishing the absolute origin coordinates with DI/DO

Absolute System ASDA-B3 10.3.4 Establish the absolute origin coordinates When the absolute coordinates are lost, the ASDA-B3 servo drive provides three ways to 10 establish the absolute origin coordinates: DI/DO, parameter setting, or the PR homing function. The following provides more details for each operation mode. 10.3.4.1 Establishing the absolute origin coordinates with DI/DO When the servo system is controlled by the controller, you can reset the absolute coordinate system with DI/DO. Once established, the pulse number is set to 0 and the PUU number is the value of P6.001. Refer to the following diagram for detailed descriptions. Description: 1.

When the controller triggers DI.ABSE (rising-edge triggered), it needs to wait for T S before proceeding to the next step. 2. After reaching T S , the controller starts to reset the coordinate system. When DI.ABSC turns on and remains on for T Q the pulse number is set to zero and the PUU number is set to the value of P6.001. DI.ABSE On Off DI.ABSC On Off Absolute position counter ( Pulse = 0; PUU = P6.001) Figure 10.3.4.1.1 Timing diagram for establishing the absolute coordinates with DI/DO The following table describes the T S and T Q delay time after triggering DI.ABSE and DI.ABSC. 10-16 T S T Q TS(ms) TQ(ms) Min (TS, TQ) P2.009 + 2 Max P2.009 + 10