Delta Electronics — 11.3.2 Interpolation Position Mode

ASDA-B3 CANopen Mode 11.3.2 Interpolation Position Mode Interpolation Position Mode requires a series of position data to complete the interpolation positioning. The difference between IP (Interpolation Mode) and PP (Position Mode) is all the 11 motion command paths of the IP mode are issued by the controller. The servo drive only follows each position that the controller issues and finally completes a motion command. Delta servo drives only support synchronous operation which is the controller periodically sends the SYNC object (COB-ID = 0x80). The interpolation cycle can be set by OD 60C2h. And the controller issues the position command to the interpolation position of OD 60C1h.

Interpolation data record (60C1h) Interpolation time period (60C2h) Position limit function [PUU] Software position limit (607Dh) Speed [RPM] Trajectory generator Max torque (6072h) Max profile velocity (607Fh) limit function Position demand value (60FCh) Quick stop deceleration Acceleration limit function [ms] Filter P1.008 P1.025 - (6085h) E-Gear ratio 6093h sub1 6093h sub2 P1.028 P1.036 P1.068 Position control Speed control Torque control Servo motor Controlword (6040h) loop loop loop Torque actual value (6077h) M Position window (6067h) Position window time (6068h) Encoder Statusword target reached (6041h) Window compara- window comparator Position + - 6093h sub2 6093h sub1 Following error actual value (60F4h) tor Position actual value (6064h) E-Gear ratio Position demand value - + Following error window (6065h) (6062h) 11-21 Velocity actual value (606Ch) Following error comparator