ASDA-B3 Troubleshooting 12 12-15 AL018 Abnormal encoder signal output Trigger condition and cause Condition: output pulse frequency of the encoder is higher than the maximum output frequency of the hardware. Cause: 1. Pulse resolution of the encoder is set too high. 2. There is interference or cable damage causing communication error. 3. Encoder error. Checking method and corrective action 1. The setting of P1.076 and P1.046 should follow these requirements: P1.076 > motor speed and Motor speed × P1.046 × 4 How to clear the alarm? 1. DI.ARST 2. Contact the distributor. AL020 Serial communication timeout Trigger condition and cause Condition: RS-485 communication error. Cause: 1.
Improper setting of the timeout parameter (P3.003). 2. Servo drive has not received the communication command for a long time and has timed out (refer to P3.003). Checking method and corrective action 1. Check and correctly set the value for the communication timeout parameter. 2. Check if the communication cable is loose or broken and make sure it is correctly wired. How to clear the alarm? DI.ARST