Delta Electronics — 12.2 Causes and corrective actions

Troubleshooting ASDA-B3 AL099 DSP error Trigger condition 12 and cause EEPROM is not reset after DSP firmware is updated. Checking method and corrective action Check if the firmware is updated. Set P2.008 to 30 first and then set it to 28. Next, cycle power on the servo drive. Contact Delta if this error persists. How to clear the alarm? Set P2.008 to 30 and then 28. Cycle power on the servo drive. 12-34 AL111 Buffer overflow occurs when receiving SDO Trigger condition and cause SDO Rx Buffer overflows (the servo drive receives more than two SDOs within 1 ms). Checking method and corrective action Check if the servo drive (master) receives or sends more than one SDO within 1 ms.

How to clear the alarm? NMT: reset node, 0x6040 fault reset, or DI.ARST. AL112 Buffer overflow occurs when receiving PDO Trigger condition and cause PDO Rx Buffer overflows (the servo drive receives more than two PDOs of COBID within 1 ms). Checking method and corrective action Check if the servo drive (master) receives or sends more than one PDO of COBID within 1 ms. How to clear the alarm? NMT: reset node, 0x6040 fault reset, or DI.ARST. AL121 Object’s index does not exist when accessing PDO Trigger condition and cause When the servo drive receives the PDO from the controller, the specified object’s index number is incorrect so that the servo drive cannot identify it.

Checking method and corrective action 1. Check if the object’s index number for PDO mapping of the controller is correct. 2. If the index number is correct, it means this specified object is not supported by the servo drive. Check if it is necessary to use this object or if you can substitute it with a different object. How to clear the alarm? NMT: reset node, 0x6040 fault reset, or DI.ARST.