Delta Electronics — 12.2 Causes and corrective actions

ASDA-B3 Troubleshooting 12 12-33 AL08B Auto-tuning function - pause time is too short Trigger condition and cause Condition: the pause time is too short when the controller is the command source in the auto-tuning procedure. The auto-tuning algorithm requires a certain amount of time to perform the calculation. The tuning result is affected if the pause time is too short. Cause: pause time in the cycle is too short. Checking method and corrective action 1. For a reciprocating motion between two points, pausing is required on the return, which has to be longer than 1 second. 2.

For rotation in a single direction, pause time is required when the motor rotates a certain number of cycles (> 2 cycles). How to clear the alarm? DI.ARST AL08C Auto-tuning function - inertia estimation error Trigger condition and cause Condition: inertia estimation error occurs when the servo drive starts the auto-tuning procedure. Cause: 1. Acceleration or deceleration time is too long. 2. Rotation speed is too slow. 3. Load inertia of the machine is too large. 4. Inertia variation of the machine is too drastic. Checking method and corrective action 1. The time for the motor to accelerate from 0 rpm to 3,000 rpm or decelerate from 3,000 rpm to 0 rpm must be within 1.5 seconds. 2.

The slowest speed must be no less than 200 rpm; above 500 rpm is suggested. 3. The load inertia should be less than 50 times the motor inertia. 4. Avoid applications that require drastic variation in the inertia. How to clear the alarm? DI.ARST