Troubleshooting ASDA-B3 AL088 Servo function operational warning Disable the filter if it is not required, such as the low-pass filter (P1.006 - P1.008), 12 moving filter (P1.068), low-frequency vibration suppression (P1.025 - P1.028), How to clear the alarm? vibration elimination (P1.089 - P1.094), Notch filter (1 st to 5 th sets), motor hard stop (torque percentage) (P1.057), and percentage of friction compensation (P1.062). 12-32 AL089 Current detection interference Trigger condition and cause Condition: current detection interference. Cause: current detection in the servo drive is affected by an external interference source.
Checking method and corrective action Check the environment around the servo drive to see if there is any interference source. How to clear the alarm? 1. Remove or reposition the interference source. 2. Set P2.112 [Bit 1] to 0 to disable AL089. 3. If the issue persists, send your servo drive back to the distributor or contact Delta. AL08A Auto-tuning function - command error Trigger condition and cause Condition: no command is issued when the servo drive starts the auto-tuning procedure. Cause: 1. When the command source is the controller, neither the controller nor the position register issued the command. 2.
When the command source is the servo drive, position 1 and 2 specify the same position. 3. The signal cable is not connected or incorrectly connected so that the servo drive cannot receive the command. Checking method and corrective action 1. Make sure a command is being issued. 2. Make sure the wiring between the controller and servo drive is correct. How to clear the alarm? DI.ARST