Troubleshooting ASDA-B3 AL304 IP mode command failure Condition: the internal command is in error in IP mode. 12 Trigger condition and cause Cause: the IP command fails. Checking method and corrective action The computing time takes too long. Disable the USB monitoring function. How to clear the alarm? NMT: reset node or 0x6040 fault reset. 12-44 AL305 SYNC period error Trigger condition and cause Condition: CANopen 301 Obj 0x1006 Data Error. Cause: SYNC period is in error. Checking method and corrective action Check the value of 0x1006. If it is smaller than or equal to 0, this alarm occurs. How to clear the alarm? NMT: reset node or 0x6040 fault reset.
AL35F Emergency stop during deceleration Trigger condition and cause DI(0x47) is rising-edge triggered, then the motor decelerates to 0 and AL3CF occurs. Checking method and corrective action Check if any of the parameters P2.010 - P2.017 and P2.036 - P2.040 is set to DI(0x47) and is triggered. How to clear the alarm? Cycle power on the servo drive. AL380 Position offset alarm for DO.MC OK _ Trigger condition and cause DO.MC OK is on and then goes off. _ Checking method and corrective action Refer to the description of P1.048. After DO.MC OK is on, DO.MC OK goes off _ _ because DO.TPOS turns off.
There might be an external force causing the position deviation of the motor after positioning is complete. Disable this alarm by setting P1.048.Y to 0. How to clear the alarm? DI.ARST