C8.3 Industrial Cooling Fan Belt Tensioner Section 8 - Maintenance Procedures at 600 Hours or 2 Years Page 8-9 Check the tensioner pulley and body for cracks. If any cracks are noticed, the tensioner must be replaced. Refer to a Cummins Authorized Repair Facility. Check the tensioner for dirt buildup. If this condition exists, the tensioner must be removed and steam-cleaned. Check that the bottom tensioner arm stop is in contact with the bottom tensioner arm stop boss on the tensioner body. If these two are not touching, the tensioner must be replaced. Inspect the tensioner for evidence of the pivoting tensioner arm contacting the stationary circular base.
If there is evidence of these two areas touching, the pivot tube bushing has failed and the tensioner must be replaced. A worn tensioner that has play in it or a belt that “walks” off its pulley possibly indicates pulley misalignment. NOTE: Maximum pulley misalignment is 3 degrees. This measurement can be taken with a straightedge and an inclinometer. Install the belt.