SERIES 60 SERVICE MANUAL 12.7.2 Chassis Dynamometer Room Ventilation Recommendations For accurate dynamometer readings during a Series 60 engine run-in, the chassis dynamometer room must be properly ventilated. See Figure 12-1. Figure 12-1 California Proposition 65 Warning If an engine is tested on a dynamometer located in an area without proper ventilation, the engine will be subject to high ambient air temperatures. High air inlet temperatures can result in false low power readings on the dynamometer. To help ensure accurate dynamometer readings, the dynamometer room should have a ceiling-mounted fan with a 850 to 1133 m 3 /min (30,000 to 40,000 ft 3 /min) capacity.

This will provide proper ventilation of exhaust gases and heat radiated by the operating engine. In situations where air circulation and proper room cooling are questionable, Detroit Diesel recommends the use of an additional 368 m 3 /min (13,000 ft 3 /min) or greater capacity barrel-type ram air fan. This should be portable so that it can be conveniently placed three to five feet (approximately one to two meters) in front of the truck and aimed directly at the charge air cooler. All information subject to change without notice. (Rev. 2005) 6SE483 0507 Copyright © 2005 DETROIT DIESEL CORPORATION 12-17