SERIES 60 SERVICE MANUAL Fuel is stored in the fuel tanks at a pressure as high as 24,821 kPa (3,600 psi). The fuel passes through high pressure fuel shutoff valves, typically controlled by both DDEC and OEM systems, through primary fuel filters to the high pressure regulator. The pressure is reduced by the high pressure regulator to approximately 758 kPa (110 psi). Flow continues through the secondary fuel filter, through the DDEC controlled low pressure fuel shutoff valve on to the low pressure regulator. The low pressure regulator is balanced to the air system at the inlet to the fuel mixer assembly.
It maintains outlet fuel pressure slightly higher than turbo boost pressure at the mixer inlet. Fuel from the regulator passes through the PSV, enters the venturi mixer and is mixed with incoming air. Air flow through the venturi creates a pressure drop at the throat of the venturi that increases and decreases in proportion to air flow. This pressure differential is used to draw fuel through the venturi insert, the PSV and low pressure regulator. The system is sometimes referred to as a demand system. Increases in pressure drop across the venturi increase the demand for fuel flow required to maintain the fuel outlet pressure at the low pressure regulator.
All information subject to change without notice. (Rev. 2005) 6SE483 0507 Copyright © 2005 DETROIT DIESEL CORPORATION 2-221