www.WorkshopManuals.co.uk 9803/3280 Purchased from www.WorkshopManuals.co.uk Issue 1 Section B Body & Framework Section B 10 - 5 10 - 5 Fault Finding Air Conditioning - System Diagnosis (cont'd) No Refrigerant Circulation Gauge Readings: Low Side Gauge - Zero to negative. High Side Gauge - Low. Other symptoms: Receiver-Drier - Frost or moisture on tubes before and after receiver-drier. Diagnosis: Refrigerant flow obstructed by dirt, moisture or gas leakage from expansion valve heat sensing tube. Correction: 1. Evacuate A/C system. 2. Check heat sensing tube at expansion valve. Replace expansion valve if necessary. 3. Remove expansion valve and attempt removal of dirt.
If dirt cannot be removed, replace expansion valve. 4. Replace receiver-drier. 5. Charge system with R-134a. 6. Operate system and check performance. LOW SIDE (Blue) HIGH SIDE (Red) Zero to negative Low 60 7 0 3501201101000908 150 2 0 0 250 20304050 350003 100 50 400 10 0 0 3 0 450 500 A268050 LOW SIDE - -1.0 bar (-1.1 kgf/cm2)(-15 lbf/in2) HIGH SIDE - 5.4 bar (5.5 kgf/cm2)(78 lbf/in2) Insufficient Cooling of Condenser or Refrigerant Overcharge Gauge Readings: Low Side Gauge - High. High Side Gauge - High. Other symptoms: Sight Glass - No bubbles visible even at lower engine RPM. Diagnosis: Refrigerant overcharge, condenser cooling fins clogged with dirt or cooling fans malfunctioning.
Correction: 1. Clean condenser cooling fins. 2. Check cooling fan operation. 3. Evacuate A/C system. 4. Charge system with R-134a. 5. Operate system and check performance. LOW SIDE (Blue) HIGH SIDE (Red) High High 60 7 0 3501201101000908 150 2 0 0 250 20304050 350003 100 50 400 10 0 0 3 0 450 500 A268060 LOW SIDE - 3.0 bar (3.0 kgf/cm2)(43 lbf/in2) HIGH SIDE - 22.1 bar (22.5 kgf/cm2)(320 lbf/in2)