Air Conditioning - Refrigerant Charging and Discharging Note: The procedures for refrigerant charging and discharging must only be carried out by qualified service personel who have received specialist training on the air conditioning system. ! WARNING The air conditioning system is a closed loop system and contains pressurised refrigerant. No part of the system should be disconnected until the system has been discharged by a refrigeration engineer or a suitable trained person. You can be severely frostbitten or injured by escaping refrigerant.
4-3-4-1/2 Evacuating (Vacuuming) This procedure follows on from the ‘Recovery’ process and is necessary to ensure proper refilling of the system with refrigerant. Lo Hi To avoid leakage in the vacuum system itself, DO NOT use extensions to the yellow hose (use standard 2 metre length). To system Low Pressure port. Valve OPEN To system High Pressure port. Valve OPEN 1 Recover all refrigerant from the system as described in Refrigerant Recovery . 2 Close all valves and connect the manifold as shown. Connect the blue hose to the system low pressure port and the red hose to the high pressure port. CPSVG100 Vacuum guage (If used) 3 Connect the yellow hose to the vacuum pump.
4 Open manifold valves. Vacuum Pump 5 Switch on the vacuum pump until 740mm (29 in) mercury vacuum reads on both gauges. A396780 6 Maintain suction for approximately 30 minutes. 7 Close valves and remove equipment. Notes: If the vacuum falls rapidly the system is leaking. Check all connections and reseal. If the point of leakage is not obvious, recharge the system and test again. Refer to Service Procedures, Air Conditioning - Leak Testing . Achievable vacuum will vary with altitude. Maximum gauge reading will be 25mm (1 in) less for every 305 metres ( 1000 feet) above sea level.
9803/3280 Purchased from www.WorkshopManuals.co.uk Issue 1 Section B Body & Framework Section B 20 - 3 20 - 3 Service Procedures