JCB — Binary Pressure Switch Testing

Air Conditioning Binary Pressure Switch Testing The binary pressure switch assembly comprises a low pressure switch designed to open at 1.96 bar (28.4 lbf/in 2 ) and a high pressure switch designed to open at 27.5 bar (400 lbf/in 2 ) When the refrigerant pressure is within the 1.96 and 27.5 bar limits the switches will be closed and providing the freeze protection thermostat and ON/OFF switches are closed, a current will be supplied to the field coil of the clutch. Through electro- magnetic action the field coil clutch will be pulled towards the compressor's clutch and the refrigeration cycle will commence.

If the fault finding table indicates that the pressure switch assembly is defective the fault may be electrical or due to incorrect system pressure. Refer to Checking Refrigerant Charge Level . If the refrigerant charge level is OK use the following electrical test procedures. 1 Switch the engine off so that the air conditioning system cannot operate. 2 Disconnect the binary pressure switch harness from the side console harness and connect an external 12V power supply between the pressure switch harness connector and chassis. If both pressure switches are working correctly, and the system is at the correct charge level, the compressor clutch will operate.

If the compressor clutch does not operate with the external power supply, one of the pressure switches in the assembly is faulty or the level of refrigerant charge is insufficient to close the low pressure switch. 3 Replace the pressure switch assembly. Refer to Binary Pressure Switch - Removal and Replacement . If the clutch still fails to operate check all electrical connections. 9803/3280 Purchased from www.WorkshopManuals.co.uk Issue 1 Section B Body & Framework Section B 20 - 7 20 - 7 Service Procedures