JCB — Refrigerant Charging and Discharging

9803/3280 Purchased from www.WorkshopManuals.co.uk Issue 1 Section B Body & Framework Section B 20 - 6 20 - 6 Service Procedures Air Conditioning - Refrigerant Charging and Discharging Note: The procedures for refrigerant charging and discharging must only be carried out by qualified service personel who have received specialist training on the air conditioning system. ! WARNING The air conditioning system is a closed loop system and contains pressurised refrigerant. No part of the system should be disconnected until the system has been discharged by a refrigeration engineer or a suitable trained person. You can be severely frostbitten or injured by escaping refrigerant.

4-3-4-1/2 Charging This procedure is industry recommended practice for refilling air conditioning systems with refrigerant. Evacuate the system beforehand to 740mm (29 in) of mercury. 1 Close all valves and connect the manifold as shown. Connect the blue hose to system low pressure and the red hose to system high pressure. Connect the yellow hose to the refrigerant cylinder. 2 Invert single valve cylinder on the scales and zero the scale reading (see Notes: for twin valve cylinders). 3 Slowly open the high pressure valve and allow the vacuum to draw-in refrigerant to the specified weight for the system. Refer to Technical Data. 4 Close all valves and remove the equipment.

Lo Hi To system Low To system High Pressure port. Pressure port. Valve CLOSED Valve OPEN Refrigerant Cylinder Thermal Blanket Scales A396810 Notes: Add refrigerant as a LIQUID, not as a gas. Some refrigerant cylinders have separate valves for gas and liquid. Be sure to connect to the liquid port when following the above procedure. Refrigerant can be used either in gas or liquid form. If recharging with gas follow the manufacturers instructions and recharge only via the low pressure port. DO NOT use liquid refrigerant at the low pressure port.

Add refrigerant until the scales indicate the specified weight for the system or the weight obtained when the system refrigerant was previously recovered. To speed up the process a thermostatically controlled thermal blanket can be used around the replenishing cylinder.