MAINTENANCE The amount of replacement inhibitor is determined by the length of the service interval and the cooling system capacity. Refer to the DCA4 Unit Guide for the selection of the correct filter to replenish the SCA. If coolant is added between drain intervals, additional SCA will be required. Check the coolant DCA concentration level anytime make-up coolant is added to the system. The SCA concentration must not fall below 0.13 units per liter or exceed 0.5 units per liter [0.5 units per U.S. gallon or exceed 2 units per U.S. gallon]. DCA4 Unit Guide Fleetguard Part No.
DCA4 Units DCA4 Coolant Filter WF-2070 WF-2071 WF-2072 WF-2073 WF-2074 WF-2075 WF-2076 WF-2077 2 4 6 8 12 15 23 0 DCA4 Liquid DCAGOL DCA80L 4 (1 Pint) 1760 (55 US gal) DCA4 Powder DCA95 20 DCA4 Precharge and Service Filters System Capacity Precharge Filter Service Filter (See NOTE 1) (See NOTE 3) Gallons 5-7 8-10 11-15 16-20 21-30 31-50 WF-2072 WF-2070 WF-2073 WF-2071 WF-2074 WF-2071 WF-2075 WF-2071 WF-2076 WF-2072 (See NOTE 2) WF-2073 NOTE 1 - After draining and replacing coolant, always precharge the cooling system to maintain the SCA concentration between 1 .O and 2.0 units per 3.8 e (1 US gal). NOTE: When performing service which requires draining the cooling system, discard the coolant.
Reusing coolant can introduce contaminates or over concentrated chemicals, resulting in premature failure of cooling system components. NOTE 2 - To precharge cooling systems larger than 114 r? (30 gal) do the following: l Install appropriate service filter listed in the above table based on cooling system capacity. Example: 95 gal (360 P) cooling system capacity -15 Units (1) WF-2075 Filter 80 Units 3-15