2-31 BEFORE CHARGING If the ampere capacity at the charging location is insufficient because other electrical appliances are being used, ask an electrical work contractor to provide an exclusive circuit for the charger. This circuit should be provided with circuit breakers or fuses having the capacities shown on P2-27. TAP Changer Setting 1. Measure with a circuit tester the supply voltage used for charging. Circuit tester range: AC(250 V or 1000 V) Note: Measure the supply voltage at night (or during recess when electrical appliances are not used.) 2. Set the tap charger (1) Remove the cover of each tap.

(2) Select the appropriate tap according to the supply voltage measured in step 1 above. (3) Manually close the magnetic switch, and measure the voltage at each tap terminal. 200 V 400 V Note: The tap of the 200 V type is set to 220 V at time of shipment. Tap changer setting shall be made for the U, V and W phases. After setting the tap changer, be sure to check the battery charging status (specific gravity and fluid level) for about a week to confirm proper tap setting.

Tap Measured voltage 200 V 199 V or less 210 V 200 to 209 V 220 V 210 to 219 V 230 V 220 to 229 V Tap Measured voltage 340 V 339 V or less 360 V 340 to 359 V 380 V 360 to 379 V 400 V 380 to 399 V 420 V 400 to 419 V 440 V 420 to 439 V 460 V 440 to 459 V