2-48 Tap Changer Setting 1. Measure with a circuit tester the power supply voltage to be used for charging. Circuit tester range: AC (250 V or 1000 V) Note: Measure the power supply voltage at night (or, if that is impossible, during a time when electrical appliances are not being operated). 2. Set the tap changer (1) Remove the cover of each tap. (2) Select the appropriate tap corresponding to the power supply voltage measured in step 1 above. (3) Manually close the magnetic switch, and measure the voltage at each tap terminal. 200 V 400 V Note: Tap are set to 220 V at the time of shipment. Be sure to set the changer for phases U, V and W.
For about a week after tap changer setting, keep track of the battery charging state (specific gravity and electrolyte level) to make sure the tap setting is appropriate. Tap Measured voltage 200 V 199V or less 210 V 200 to 209 V 220 V 210 to 219 V 230 V 220 to 229 V Tap Measured voltage 340 V 339V or less 360 V 340 to 359V 380 V 360 to 379V 400 V 380 to 399V 420 V 400 to 419V 440 V 420 to 439V 460 V 440 to 459V