WTEC III ELECTRONIC CONTROLS TROUBLESHOOTING MANUAL CODE 24 XX — SUMP FLUID TEMPERATURE (Figure 6–7) DIAGNOSTIC CODES Copyright © 2001 General Motors Corp. 6–39 Main code 24 indicates the ECU has detected either a high or low fluid temperature in the transmission sump (via the sump temperature sensor in the internal harness). All shifts are inhibited when code 24 12 is set (only Neutral range operation is allowed). No upshifts are allowed above a calibration range when code 24 23 is set. All inhibits are cleared when the temperature conditions are normal.
A related code is 33 12 which indicates a temperature reading outside the usable range of the sensor and indicates a probable sensor failure. NOTE: When an ECU with a version 8 calibration (CIN=0A...) is used with a TransID 2 transmission, 24 XX codes are set because the ECU does not have the proper calibrations for the TID 2 thermistors. The ECU calibration must be updated to version 8A or later (CIN=0B). TransID (TID) information related to thermistor changes is in Paragraph 1–11 and detailed troubleshooting information for TID 2 thermistors is shown in Appendix Q. Main Code Subcode Meaning 24 12 Sump fluid temperature cold 24 23 Sump fluid temperature hot A.
Active Indicator Clearing Procedure: • Power down • Manual • Self-clearing NOTE: Before troubleshooting, read Paragraph 6–6. Also, check the ECU input voltage. B. Troubleshooting: Code 24 12: 1. If the outside temperature is between –32˚C (–26˚F) and –7˚C (+19˚F), the ECU will allow re- verse, neutral, and second-range start operation. Only hold override upshifts are allowed. (See Table 6–4 on next page.) The sump must be warmed to an acceptable temperature to avoid logging codes and transmission diagnostic response. NOTE: Code 24 12 can result when the +5V line (wire 124) which powers the sump temperature sensor is shorted to ground.
Wire 124 also powers the TPS, OLS, RMR, retarder temperature sensor, and shift selectors and is present in all three ECU connectors. 2. After allowing the temperatures to normalize, if ambient temperature does not match the sump temperature reading (check using diagnostic tool), compare resistance versus sump fluid temper- ature. Refer to Figure 6–8 for TID 1 thermistors and Appendix Q for TID 2 thermistors. If resis- tance check is acceptable, then check the sensor wiring for opens, shorts, or shorts-to-ground. 3. If the sensor wiring is satisfactory, drain the fluid, remove the control module, and replace the temperature sensor (refer to appropriate transmission Service Manual). CAUTION:
Using an unmatched ECU/CIN combination may result in additional codes being set or in transmission clutch damage. Using an ECU from another vehicle is not a recommended procedure where the test will involve driving the vehicle. This is because the stored adaptive information is tuned to the original vehicle's transmission and those adaptive settings may not perform as expected in another vehicle. Transmission performance could be worse and damage to the clutches may occur. Main Code Subcode Meaning 24 12 Sump fluid temperature cold 24 23 Sump fluid temperature hot