12. OPERATION 12.5 CHANGING VOLTAGE (EG125BS-2) Ay WARNING e When opening engine. the protective cover, be sure to stop the e If the shorting bar is connected wrongly, the generator may burn. Be careful. Clamp the shorting bar with the nuts securely. If it is loosened, it will heat up and cause a fire. Set the rated voltage as follows according to the type of work and the district where the generator is used. 50 Hz 200 V, 400 V 60 Hz 220 V, 440 V Select a desired output voltage according to the following procedure. 1. Remove the protective cover of the voltage changeover plate on the right side of the control box viewed from front. | 5 2. 3. @ :
= ° 5 1) 1 Change the output voltage by changing the connection of the terminal of the voltage changeover plate and shorting bar @. / [| After connecting shorting bar @, change voltage changeover switch @) according to the connection of the shorting bar. sar 8460 200V/220V connection diagram Turn the voltage changeover switch to the 200V position. — c—, | 2 by = 2 | 2 bZ Lo AB7 16470 e 400V/440V connection diagram Turn the voltage changeover switch to the 400V position. — 0 At Uroy ° V2 0 Z| | | We o0 AB716480 2-35