eng — 12.6 PARALLEL-ARRANGED OPERATION

12. OPERATION 12.6 PARALLEL-ARRANGED (EG125BS-2) OPERATION Since this machine is equipped with the following, two or more sets can be operated in parallel: e@ e Synchronizing switch (Single/Parallel change-over switch) Synchronizing lamp | e Crosscurrent compensation When quencies, circuit operating two or more voltages, and phases generators must be in parallel, their fre- set to the same values. Operating the generators under this condition is called synchronized operation. NOTICE Take care not to let the fuel run out while the generators are running.

12.6.1 CONNECTION METHODS @ Terminals of the same symbols (U - U, V - V, W - W) If the terminals of different symbols are connected to each other, the generators and loads may be damaged and motors may rotate in reverse. As shown in the diagram, connect the cables so that the terminals of the same symbols (U. V. W) on the terminal and load terminal boards 2-36 are connected together. —_Oc O <= p——— OE oc Ox e—tO= Oc e@ Terminal O is not for grounding. If it is connected to the ground, workers may suffer electric shocks and the machines may be damaged. Never connect terminal O to the ground. POE Ay WARNING ae AAT16490