5 Control Heads Single Function Control Head Calibration - CH4400 or CH5600 This calibration procedure is for single function controls. This type of control has shift for one engine on a lever and throttle for one engine on a different lever. The CH4400 and CH5600 are typical of this type of control. Single Function - Single Engine Controls With the system OFF (no power on the CAN Bus) press and hold the NEUTRAL button on the CP1100 Control Panel and turn the power ON. The Neutral lamp will blink. Move the throttle lever to the FULL THROTTLE (WOT) position and press the SELECT button. The select lamp will turn on. Move the throttle lever to the IDLE position. The neutral lamp will blink.
Press the SELECT button. The select lamp will turn on. Move the shift lever to the FORWARD position. The neutral lamp will blink. Press the SELECT button. The select lamp will turn on. Move the shift lever to the NEUTRAL position. The neutral lamp will blink. Press the SELECT button. The select lamp will turn on. Move the shift lever to the REVERSE position. The neutral lamp will blink. Press the SELECT button. The select and neutral lamps will both blink indicating the process is complete. Turn the power OFF to exit the calibration process. © 2011 Yanmar Marine International • Rev. 2.0 Yanmar Electronic Control Systems Technical Manual 5:29