Yanmar — Yanmar Electronic Control System Technical Manual for Classic, BY2, 6LY3, 6CX, and SY GEN III Series Engines

16 Accessory Information Fire Suppression Systems Connection Details Shut-down Alarm cables CE41800 (SY GEN III) and CE42800 (6LY3, 6CX) are designed to assist in the connection of a fire control system. They allow easy access to the engine ignition wire and the emergency stop line. There are a number of variations of the fire systems and how they can be connected. For the fire control system to work properly it is important for the installer to understand the emergency stop and the normal shut down process of the engine and how multiple engines and gen-set equipment interact with the fire control system. The following items enter the picture.

The normal shut down process of the 6LY3, 6CX, initiated by the ignition switch, can take 3 to 5 seconds to shut down the engine. The emergency stop of the 6LY3, 6CX stops the engine immediately. This should only be used for an emergency as restart data is lost. The emergency stop on the SY GEN III stops the engine immediately and does not effect restart. On the 6LY3, 6CX, in the event of a fire, it is necessary to use the emergency stop to assure the effectiveness of the fire control system. The normal 3 to 5 second shutdown process could cause a significant loss of the fire suppression chemical.

All equipment in the engine room that moves air through the engine room must be considered with the fire control system. This can include the main engines, the gen-set, and engine room blowers. The typical connection of the fire control system is as follows: Turning on any ignition signal will activate the fire suppression system and permit all engines and blowers to operate. If a fire occurs and the fire bottle sensor opens all engines and blowers will shut down. This is the expected and correct operation. © 2011 Yanmar Marine International • Rev. 2.0 Yanmar Electronic Control Systems Technical Manual 16:3