OM2049 2/13 Safety - Section 20 Page 20-21 4. Measure voltage on all capacitors as described in “Measuring Dc Voltage On Capacitors” on page 18. Discharge any capacitors that show voltage. Voltages in excess of 1500 VDC may be present. Any measurement and/or protective equipment used must be rated at 2000 VDC minimum. 5. If all capacitors read discharged, verify that the meter is functioning correctly using site- approved procedures. If so, proceed to the next section. Verify functionality of the measurement equip- ment using site-approved procedures both before and after performing control group mea- surements.
Failure to observe these precautions may result in death or serious personal injury. FIGURE 20-12. APPLICATION OF GROUNDING STICKS TO CAPACITOR TERMINALS