SYSTEM TROUBLESHOOTING CHART (CONT’D) Gauge Pressure Related Troubleshooting Normal compressor suction (low side) and discharge (high side) pressure at ambient temperatures of 86-96 degrees F (30-38 degrees C) and compressor speed of approximately 2000 RPM are: High pressure side pressure: 210-265 PSI Low pressure side pressure: 15-33 PSI As a rule of thumb the high side pressure will be around eight times greater than the low side pressure. 442 Excavator 70-100-2 Service Manual POSSIBLE CAUSE INSPECTION SOLUTION Low pressure side too high. The low pressure side pressure normally becomes too high when the high pressure side pressure is too high.
As this is explained below, the following inspection is only used when the low pressure side is too high. 1. Expansion valve opens too far. Frost is present on the suction hose. Replace expansion valve. 2. Defective compressor The high and low pressure side gauge pressures equalize when the magnetic clutch is disengaged. Replace compressor. Low pressure side too low. 1. Low refrigerant charge The high side pressure will be low and bubbles may be present in sight glass on receiver drier. Repair any leaks and recharge the refrigerant to the correct level. 2. Clogged or closed expansion valve. The expansion valve’s inlet side is frosted. Moisture or other contaminants can be the cause.
Clean or replace the expan- sion valve. 3. Restriction between drier and expansion valve. Frost on the line between drier and expansion valve. A negative low pressure reading may be shown. Flush system or replace hose. 4. Thermostat malfunction The evaporator is frozen. Replace thermostat. High pressure side too high. 1. Poor condenser performance Dirty of clogged condenser fins. Condenser fans not oper- ating. Clean fins, and/or repair the fan. 2. Excessive refrigerant. The high pressure side pressure will be high. Use refrigerant recovery equipment to capture excess refrigerant. Charge to the correct refrigerant level. 3. Excessive oil charge. The high pressure side will be high.
Evacuate system. Remove oil from condenser and com- pressor. Measure oil from compressor and add cor- rect oil charge back into compressor. Flush system with nitrogen. Replace drier. 4. Air in system. Pressure side will be high. Evacuate and recharge with refrigerant. 5. Restriction in drier condenser or high pressure line. High pressure side will be high, and low pressure side will be low. Evacuate and flush system replacing defective parts.