COOLING SYSTEM, AIR-TO-AIR CHARGE COOLING 8.10.3 ENVIRONMENTAL AND OPERATING CONDITIONS Consider both environmental and operating modes of the installation when designing the cooling system. Reserve capacity and special selection of components are required for operation in the following extremes:
Hot or cold ambient temperatures High altitude Space constraints Noise limits Tilt operation or installations Arid, damp, dusty, oily, windy conditions Long-term idle, full load, peak torque operation Long-term storage or standby operation Indoor/outdoor operation Serviceability limitations Infrequent maintenance intervals Severe shock or vibration System deterioration Multiple engine installations The heat rejected to the coolant generally increases when engine performance is reduced due to external conditions. Engine performance is adversely affected by:
High air restrictions High exhaust back pressure High air inlet temperature Altitude 8.10.3.1 Ambient Temperature The ambient temperature in which an engine will be operated must be considered when designing the jacket water (JW) and CAC systems. The worst case cooling conditions are often at the highest expected ambient temperature. Operating in extremely cold ambient, at light loads, or during extended idling will require conservation of heat energy. Coolant temperatures must be maintained near the thermostat opening value. This controls engine oil temperature at a satisfactory level for good engine performance and reliability.