COOLING SYSTEM, AIR-TO-AIR CHARGE COOLING Figure 8-16 Shell and Tube Heat Exchangers Consider the following guidelines when selecting a shell and tube heat exchanger: Minimize restriction to the engine cooling system by keeping the number of tube side passes to a minimum Prevent tube erosion by keeping tube velocities below 7 ft./sec. Shell side flow velocities should be higher than 1 ft./sec. Typically, in industrial applications, tubes are copper and the shell is steel. Choose more corrosion resistant materials if fluids are more corrosive.

8.13 FAN SYSTEM RECOMMENDATIONS AND FAN SELECTION Proper selection and matching of the fan and radiator as well as careful positioning will maximize system efficiency and will promote adequate cooling at the lowest possible parasitic horsepower and noise level. Obtain radiator and fan performance curves from the manufacturer to estimate air system static pressure drop and determine if a satisfactory match is possible. Installations using the largest fan diameter possible, turning at the lowest speed to deliver the desired air flow, are the most economical. NOTE: Fan blades should not extend beyond the radiator core. Blades that reach beyond the core are of minimal or no benefit.

Other important considerations include: 8-28 All information subject to change without notice. DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION