TROUBLESHOOTING / Troubleshooting B Purging Procedure IMPORTANT: Never mistake the charge hose connections. 1. Close the high and low pressure valves on the gauge manifold (Parts Number 4360564). Connect the high-pressure-side charge hose and the low-pressure-side charge hoses to the high-pressure-side charge valve (“D” marked) and to the low-pressure-side charge valve (“S” marked) located on the compressor, respectively. Connect the charge hose located on the center of the manifold bottom to the vacuum pump (Parts Number 4360565). Gauge Manifold Low Pressure Charge Hose High Pressure Valve High Pressure Charge Hose NOTE: Vacuum Pump Joint Adapter (Parts Number 4360566). 2.
Fully open the high pressure and low pressure valves in the gauge manifold. Perform purging for 10 minutes or more by operating the vacuum pump. W115-02-10-005 S Low Pressure Side Compressor High Pressure Side D T142-02-05-018 Fully Open W115-02-10-005 T5-6-100 Low Pressure Valve Pressure Hose V acu Fully Open In Op