Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 5 - 18 Section 5 – Maintenance Procedures CFP83 Series Procedure 23 Change Lubricating Oil and Filters WARNING To reduce the possibility of personal injury, avoid direct contact of hot oil with your skin. WARNING Some state and federal agencies have determined that used engine oil can be carcinogenic and cause reproductive toxicity. Avoid inhalation of vapors, ingestion, and prolonged contact with used engine oil. If not reused, dispose of in accordance with local environmental regulations. WARNING If no oil pressure is noted within 15 seconds after the engine is started, shut down the engine to reduce the possibility of internal damage.

CAUTION For composite oil pans, always use a new sealing washer on the oil drain plug. Hold the external locking nut in place while tightening the oil drain plug. Lubricating Oil and Filter Change Interval Engine oil becomes contaminated and essential oil additives are depleted with use. The amount of contamination is related to the total amount of fuel and oil consumed. The oil change interval for turbocharged engines is every 3 months or 250 hours. Change the oil and the filters to remove the contaminants suspended in the oil. NOTE : If the lubricating oil is drained from the oil pan to make an engine repair, new oil must be used. Do not use oil after it has been drained from the oil pan.

Laboratory and field tests have determined that, when using the recommended quality oils and filters, a turbocharged engine in good condition and equipped with a by-pass oil filter can consume 255 U.S. gallons of fuel for each U.S. gallon of oil in the oil system before the maximum level of oil contamination is reached. NOTE : Cummins Engine Co. Inc, does not recommend exceeding 25,000 miles and/or 600 hours on oil change intervals. Drawing No. 9777, Section 5, Rev. 02-07