Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 5 – Maintenance Procedures Page 5 - 21 CFP83 Series Check and clean the oil drain plug threads and sealing surface. Install the oil drain plug. Torque Value: 50 N•m [37 ft-lb] NOTE : Use a high-quality 15W-40 multiviscosity lubricating oil, such as Cummins Premium Blue®, or its equivalent, in Cummins engines. Choose the correct lubricating oil for your operating climate as outlined in Section 5. Fill the engine with clean oil to the proper level. NOTE : Capacities assume standard pan. Total system assumes standard pan plus filter. NOTE: When filling the oil pan, use the fill tube on the side of the engine rather than on top of the rocker lever cover.

WARNING If no oil pressure is noted within 15 seconds after the engine is started, shut down the engine to reduce the possibility of internal damage. Operate the engine at idle to inspect for leaks at the filters and the drain plug. Drawing No. 9777, Section 5, Rev. 02-07