Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 5 – Maintenance Procedures Page 5 - 47 CFP83 Series Every Two Years or 2000 Hours All checks or inspections listed under daily or previous maintenance intervals must also be performed at this time, in addition to those listed under this maintenance interval. General Information Procedure 35 Inspect Viscous Damper CAUTION The silicone fluid in the vibration damper will become solid after extended service and will make the damper inoperative. An inoperative vibration damper can cause major engine or drivetrain failures. Check the damper for evidence of fluid loss, dents, and wobble.

Visually inspect the vibration damper thickness for any deformation or raising of the damper front cover plate. If any variations or deformations are detected, refer to the Troubleshooting and Repair Manual for detailed inspection procedures. Viscous dampers have a limited lift. The maximum damper life specifications are located in Maintenance Specifications. Procedure 36 Inspect Water Pump Inspect the water pump for drive pulley wobble and grease or water leakage around the water pump shaft. Replace with a new or rebuilt, pre-lubricated unit as necessary. Refer to the Troubleshooting and Repair Manual for more information. Drawing No. 9777, Section 5, Rev. 02-07