Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-17 CFP83 Series Coolant Heat Exchanger Removal/Installation (Cont) Remove the Upper Engine Coolant Hose from the heat exchanger. Remove the Lower Engine Coolant and Fill Hose from the heat exchanger. Remove the Coolant Vent Hose from the heat exchanger. Close the Raw Water Manifold Bypass Line Outlet Isolation Valve. Close the Raw Water Manifold Normal Line Outlet Isolation Valve. CFP83-F10, F20, or F30 Only NOTE : If using piping supplied by Cummins Fire Power, refer to Drawing 9637 in Section 13 for raw water supply piping details. Remove the 1” NPT raw water inlet piping from the valve manifold to the heat exchanger.

Also, remove any customer-supplied raw water outlet fittings. Save these components for reuse. Drawing No. 9777, Section 7, Rev. 02-07